Three tapes, three jobs on the same joint
A medium-voltage cable splice is usually built up from more than one tape, and 3M's splicing range assigns each model a different role. Scotch Rubber Splicing Tape 23 is a 30-mil ethylene propylene rubber tape used to build conformable insulation and moisture protection around the splice. Scotch Linerless Rubber Splicing Tape 130C provides primary insulation and termination of solid dielectric cables rated through 69 kV. Scotch 2220 Electrical Stress Control Tape manages voltage distribution where cable shielding has been removed.
Because the three products work as a system, comparing them as if they were competing alternatives misses the point. The question is which layer each tape supplies, not which one is strongest.
What the published temperature rating covers
Both Scotch 23 and 130C carry a continuous temperature rating up to 90°C, and both use self-fusing ethylene propylene rubber so a wrapped layer fuses into a solid mass rather than relying only on adhesive. The practical difference is construction: 23 is a linered rubber tape that builds thickness quickly, while 130C is a linerless tape supplied for primary insulation duty, with a fusible interlayer designed for direct contact with the conductor insulation.
A 69 kV rating describes the cable system 130C is intended for, not a promise that a single layer of tape alone insulates that voltage. Splice design, layer count, and the termination procedure come from the cable manufacturer's instructions.
When 2220 enters the build
Stress-control tape is used at the point where cable shielding ends, in joints and terminations, to spread the electrical field so the transition does not concentrate stress at one edge. It is not an insulating build tape by itself; it is applied in combination with splicing tapes such as 23 and 130C according to the approved procedure.
If a drawing or specification names 2220, keep that model in the request. A general-purpose rubber tape is not an equivalent for a stress-control layer.
Confirm the cable system, not just the model
When requesting splicing tape, include the cable construction, conductor size, insulation type, voltage class, whether the job is a joint or a termination, and the splice procedure being followed. The tape model alone does not define the build; the cable system and the installation standard do.
Ask for the current manufacturer technical data sheet for the exact model and compare it with the approved procedure before ordering. Nearby model numbers are discussion starting points, not proof of interchangeability.
Splicing tape in general: what it is
Splicing tape is a self-fusing tape used to rebuild insulation, seal a joint, or manage electrical stress where a cable has been cut. The two chemistries in this family are EPR rubber, used in Scotch 23 and 130C, and silicone rubber, used in Scotch 70. Both fuse to themselves under tension, so the wrapped layers become a solid mass rather than a stack of separate layers held only by adhesive.
The same self-fusing behaviour is used outside cable joints: wrapping a hose repair, sealing a water-exposed connection, or building an insulating wrap over a bus bar. The selection method does not change for those jobs — start from the voltage class, the temperature the joint will see, and whether the tape has to insulate, control stress, or simply seal, then match the chemistry and the layer count to the job.
Three-model numbers at a glance
The verified numbers are: Scotch 23 is a 30 mil (0.76 mm) EPR rubber tape rated for continuous service to 90°C and used for insulation build and moisture sealing through 69 kV systems. Scotch 130C is the linerless EPR tape in the same family, also for primary insulation through 69 kV, without a release liner. Scotch 70 is a 0.30 mm silicone tape rated Class H to 180°C with a dielectric strength of 34 kV/mm, specified for heat and weathering rather than as the primary insulation build.
Scotch 2220 does not belong in the same column: it is a stress-control compound applied at the shield cutback to spread the electrical field, not an insulation layer. Its thickness and temperature figures are published per the data sheet, and it is always used in combination with splicing tapes such as 23 and 130C rather than on its own.
Common mistakes when choosing between the three
The most common mistake is choosing by price or by the model a colleague used last time. A cheaper tape that is the wrong chemistry or the wrong layer leaves the joint short of insulation or of stress control, and the failure shows up in service rather than on the bench. A second mistake is treating 2220 as an insulation layer: it manages the electrical field at the shield cutback and cannot replace the insulating build of 23 or 130C.
A third mistake is swapping 23 and 130C as if they were the same tape. Both are EPR and both are rated through 69 kV, but 130C is linerless and 23 carries a liner, so the handling and the wrap method differ. Follow the cable manufacturer's splice procedure for which model goes in which layer, and confirm the layer count and the application method against the current data sheet before ordering.
Send a quote request that can be checked
A useful request reads like this: cable type and voltage class; joint or termination; splice procedure reference; tape models required (for example 3M Scotch 23 and 130C); roll width and length; quantity; destination. Add the operating environment and any customer-approved supplier list.
If the build has not been finalised, say so. That lets the supplier discuss layer selection without presenting an unverified substitute as approved material.
Frequently asked questions
Can 3M 23 and 130C be substituted for each other?
Both are self-fusing EPR splicing tapes rated to 90°C continuous, but they are specified for different layers of a splice build. 130C is intended for primary insulation through 69 kV cable systems, while 23 is a general splicing and moisture-sealing build tape. Follow the cable manufacturer's splice procedure rather than substituting between them.
Is 3M 2220 used alone?
No. 2220 is a stress-control tape applied at the shield-cutback area of joints and terminations, in combination with splicing tapes such as 23 and 130C. It manages voltage distribution rather than providing the insulating build.
What temperature can 3M splicing tape withstand?
Scotch 23 and 130C are rated for continuous service up to 90°C. Confirm the exact rating and application method against the current manufacturer data sheet for the specific model and batch.
Can Scotch 2220 be used as an insulation layer?
No. 2220 is a stress-control tape applied at the shield cutback of joints and terminations to spread the electrical field. It is used in combination with splicing tapes such as 23 and 130C, and it cannot replace the insulating build those tapes provide.
How do I choose between silicone and rubber splicing tape?
Choose by duty: silicone tape such as Scotch 70 is specified where the joint must keep its insulation value at high temperature or outdoors, rated Class H to 180°C. EPR rubber tapes such as 23 and 130C are specified as primary insulation on medium-voltage splices and terminations through 69 kV.