What is Scotch 70
3M Scotch 70 is a self-fusing silicone rubber splicing tape: it has no conventional adhesive layer, and instead fuses to itself when stretched and wrapped, forming a solid, void-free silicone rubber insulation layer. It is the tape to specify when a splice, termination or bus-bar wrap must keep its insulation value at temperatures where PVC and ordinary rubber tapes no longer qualify.
The headline rating is Class H, 180°C continuous service, on a 0.30 mm (12 mil) silicone backing with a dielectric strength of 34 kV/mm. A standard roll is 25 mm wide and 9.1 m long. Because silicone rubber resists heat, ozone, weathering and tracking, Scotch 70 is used as a protective overwrap on spacer cable systems above 15 kV and wherever an outdoor or high-temperature joint needs a durable outer layer.
Key specifications to check
When buyers search for 3M Scotch 70 or scotch 70 silicone tape, the first numbers to confirm on the current 3M data sheet are the thickness (0.30 mm), the dielectric strength (34 kV/mm) and the Class H 180°C temperature rating. Check also the roll width and length per roll, since a 25 mm x 9.1 m roll covers a different joint size from a wider or longer format.
Silicone tape is applied differently from PVC tape: it must be stretched during wrapping so the layers fuse, and the wrap is usually finished with a half-lap so the fused mass has no gaps. Confirm the application method, the number of layers the joint design calls for, and whether the specification requires an overwrap or a primary insulation layer, because the two duties call for different tape choices.
Where Scotch 70 is used
Common applications include overwrap and end-sealing on spacer cable systems above 15 kV, insulation of bus bars and connections in switchgear, motor lead insulation, and high-temperature splices and terminations where the joint runs hot in normal service. It is also used as a protective outer layer over rubber splicing tape, shielding the primary insulation from heat, weather and corona.
Outdoor terminations are a natural fit: silicone rubber keeps its flexibility and insulation value after prolonged exposure to sun, rain and ozone, where a PVC overwrap would harden and crack. For the same reason Scotch 70 appears in utility, industrial and mining cable specifications wherever a joint must survive heat and weather at the same time.
Scotch 70 vs rubber splicing tape
Scotch 70 and the EPR rubber tapes Scotch 23 and 130C are often confused because all three are self-fusing, but they do different jobs. Scotch 23 and 130C are primary insulation tapes for medium-voltage splices and terminations through 69 kV, building insulation thickness and a moisture seal. Scotch 70 is a silicone tape specified for heat, weathering and tracking resistance, most often as an overwrap or in high-temperature service.
Do not substitute one for the other on the basis of price or appearance. If the splice system calls for EPR primary insulation, use 23 or 130C and add 70 only where the design requires a silicone overwrap. If the joint runs above the temperature range of rubber tape, or sits outdoors on spacer cable, the silicone construction of 70 is the reason it is specified.
Silicone vs EPR self-fusing: how the chemistry differs
Scotch 70 and the EPR rubber tapes 23 and 130C are all self-fusing, but the chemistry sets different limits. Silicone rubber in 70 is rated Class H for continuous service to 180°C, on a 0.30 mm backing with a dielectric strength of 34 kV/mm. EPR rubber in 23 and 130C is rated for continuous service to 90°C, with 23 built on a 30 mil (0.76 mm) EPR backing. The temperature gap is the reason 70 is specified for hot joints and 23 and 130C for medium-voltage primary insulation.
Chemistry also changes what the tape tolerates. Silicone rubber keeps its flexibility after prolonged exposure to sun, rain and ozone, which suits outdoor terminations and spacer cable overwrap. EPR rubber fuses into a solid moisture-resistant mass that suits primary insulation on splices and terminations through 69 kV. Choose by the duty — heat and weathering, or insulation build and moisture seal — not by which tape looks similar on the roll.
Stretch-and-fuse technique and layer order
Silicone tape only fuses when it is stretched during wrapping, so the technique is part of the specification. Stretch the tape as the data sheet and the splice procedure direct, wrap with a half-lap so the fused mass has no gaps, and keep tension even around the joint. A layer order that appears in medium-voltage practice is stress-control tape at the shield cutback first, then 23 or 130C stretched and fused as primary insulation, then 70 as the silicone outer layer where heat or weather demands it.
The layer count comes from the joint design, not from a rule of thumb. Confirm how many layers the splice procedure calls for, whether the specification requires an overwrap or a primary insulation layer, and whether the outer layer is 70 or another material — because the two duties call for different tape choices, and the wrong layer order leaves the joint short of insulation or of weather protection.
What goes wrong when the technique is skipped
The common failures are all technique failures. Wrapping without enough stretch leaves air gaps between layers, and the fused mass never forms. Using silicone tape where the joint needs EPR primary insulation leaves the splice short of insulation build, because 70 is an overwrap and high-temperature tape rather than a medium-voltage insulation build tape. Using too few layers leaves the joint below the insulation the procedure calls for.
Check the finished joint before it goes into service: the wrap should be even, with no visible gaps or loose edges, and the layer count should match the procedure. If the joint design calls for a silicone overwrap, confirm that 70 is the outer layer and that the primary insulation underneath is the EPR tape the system specifies.
How to order from a supplier
A useful Scotch 70 enquiry includes: exact model (3M Scotch 70), roll width and length, quantity, destination, and the application — spacer cable overwrap, bus-bar insulation, motor lead, or high-temperature splice. State the voltage class and the operating temperature so the supplier can confirm the tape is suitable for the joint.
Ask for the current 3M data sheet by model number and confirm the roll format matches your application procedure. For branded tape, confirm the supply channel and supporting documentation; for equivalent silicone grades, confirm the thickness, dielectric strength and Class H temperature rating before ordering.
Frequently asked questions
What is 3M Scotch 70 used for?
3M Scotch 70 is a self-fusing silicone rubber splicing tape used for high-temperature insulation, bus-bar and motor-lead insulation, and as a protective overwrap on spacer cable systems above 15 kV. It fuses to itself under tension to form a solid silicone rubber layer that resists heat, ozone and weathering.
What temperature can Scotch 70 handle?
Scotch 70 is rated Class H for continuous service up to 180°C. That is the reason it is specified where PVC and ordinary rubber tapes no longer qualify — high-temperature splices, motor leads and hot outdoor joints.
Can Scotch 70 replace Scotch 23?
No. Scotch 23 and 130C are EPR rubber tapes used as primary insulation on medium-voltage splices and terminations, while Scotch 70 is a silicone tape specified for heat and weathering resistance, most often as an overwrap. Use the tape the splice system calls for, and add 70 only where a silicone overwrap is required.
How do I choose between silicone and rubber splicing tape?
Choose by duty: silicone tape such as Scotch 70 is specified where the joint must keep its insulation value at high temperature or outdoors, rated Class H to 180°C. EPR rubber tapes such as 23 and 130C are specified as primary insulation on medium-voltage splices and terminations through 69 kV. Do not substitute one for the other on price or appearance.
How many layers of Scotch 70 does a joint need?